COMMERCIAL BUILDING SCIENCE · HEAT · AIR · MOISTURE · MEASUREMENT

Blank measurement template

ICY Cooling Science Field Record

Use one row for one direct observation or one derived result. The record preserves operating context, source class, instrument identity and uncertainty without converting screening observations into an unsupported diagnosis.

Before recording

Context makes the number useful.

The template is intentionally blank. It contains no customer record and no example reading that could be mistaken for a field result.

  1. Do not overwrite a baseline after a change; create a new row linked to the earlier record.
  2. Use ISO 8601 local date and time plus an explicit UTC offset, and synchronize instruments when sequence matters.
  3. Record SI values first. Put optional U.S. customary equivalents in a separate clearly labeled field or note.
  4. Choose one source class: literature summary, GCT field method, field observation, qualified-trade finding, owner report or derived calculation.
  5. Keep raw readings separate from calculations. Preserve formulas, input record IDs, conversions and assumptions for every derived value.
  6. Use null for a measurement not taken and explain an omission that affects interpretation. Zero is a measured value, not a blank.
  7. Identify instrument and calibration status, state dominant uncertainty contributors and do not report more digits than the method supports.
  8. Record equipment, controls, occupancy, doors and exhaust state with every environmental reading that depends on operation.
  9. Use non-sensitive project and zone references. Do not place customer identity, personal data, credentials or security-sensitive building details in a public record.
  10. Separate observed facts, reported statements, interpretations and recommended next actions.
  11. Record the safety boundary and stop condition. A missing measurement is preferable to an unauthorized or hazardous one.
  12. Close an issue only against a declared acceptance criterion, preserving failed, inconclusive and no-change results.

CSV columns

One row for one observation or reading.

ColumnUnit or formWhat to record
recordIdnoneUnique immutable identifier for this observation or calculation.
projectReferencenoneNon-sensitive project or study identifier.
siteZonenoneRepeatable location reference without unnecessary public identity.
sourceClassnoneOne of literature_summary, gct_field_method, field_observation, qualified_trade_finding, owner_report or derived_calculation.
observationTypenoneQuantity, event, document or operating response recorded.
dateTimeLocalISO 8601ISO 8601 local timestamp for the observation.
utcOffsethh:mmUTC offset associated with dateTimeLocal, such as -05:00.
observerRolenoneObserver role only; do not imply an unverified credential.
operatingStatenoneEquipment, controls, occupancy, doors and exhaust state relevant to the reading.
weatherSourcenoneOn-site instrument or identified external station and timestamp.
outdoorDryBulb°COutdoor dry-bulb temperature at the relevant time and location.
outdoorDewPoint°COutdoor dew-point temperature at the relevant time and location.
indoorDryBulb°CIndoor dry-bulb temperature at the stated sensor location.
indoorRelativeHumidity%Indoor relative humidity paired with the stated temperature and location.
indoorDewPoint°CMeasured or documented calculated indoor dew-point temperature.
surfaceTemperature°CSurface temperature with material and contact or infrared method stated.
supplyAirTemperature°CSupply-air dry-bulb temperature at the stated point.
returnAirTemperature°CReturn-air dry-bulb temperature at the stated point.
pressureReferencenoneMeasurement and reference zones plus positive/negative sign convention.
pressureDifferencePaPressure at the measurement zone relative to pressureReference.
airflowL/sMeasured airflow with geometry and method stated.
electricalPowerkWMeasured real electrical power for the identified equipment boundary.
equipmentIdnoneControlled equipment or asset reference.
instrumentIdnoneInstrument make, model and serial number or controlled asset ID.
calibrationStatusnoneCalibration date, reference and due status, or explicitly unknown.
methodIdnonePublished, manufacturer or controlled GCT method reference.
rawObservationas statedWhat was directly read, seen or reported, without a causal conclusion.
inputRecordIdsnoneIdentifiers of raw records used by a derived calculation.
derivedCalculationas statedFormula, inputs, units, conversions, assumptions and result.
uncertaintyStatementas statedQuantitative uncertainty where justified, otherwise the dominant limitations.
attachmentReferencenoneControlled file or image reference with checksum where practical.
factInterpretationBoundarynoneExplicit separation of direct observation, report, inference and qualified-trade finding.
safetyBoundarynoneHazards, stop conditions and work reserved for qualified providers.
actionTakennoneAuthorized change with actor and time, or none when no change occurred.
acceptanceCriterionas statedPredeclared requirement, threshold, tolerance and test condition.
resultStatusnoneOne of observed, pass, fail, inconclusive, not_tested or open.
reviewStatusnoneOne of draft, field_checked, qualified_provider_reviewed or publication_reviewed.
reviewNotenoneReviewer role, scope reviewed, date and unresolved issue without invented credentials.
Use safely

This record does not authorize roof access, opening energized equipment, disturbing refrigerant systems or entering a hazardous space. Qualified parties, site rules, manufacturer instructions and applicable law control the work.